Fault diagnosis and maintenance of PSI and vlc/vls series of motor soft starter

(I) quick look-up table of fault maintenance see table for psi and vlc/vls fault maintenance

table fault maintenance quick look-up table

possible indicators of problems can be the cause of mechanical spring fatigue tester TPJ series energy solution when the power is turned on, one main fuse is blown or the circuit breaker is disconnected

the "fault" and "shunt trip" indicators are on

short circuit inspection at the input end of the power source troubleshooting short circuit thyristor fault refer to the thyristor inspection procedure, Power off and check scr

the fuse is disconnected or the circuit breaker is disconnected when starting

"fault" and "short circuit" lights up

"fault" and "lack of phase" lights up

line short circuit, motor or cable grounding fault

check and eliminate the short circuit or motor grounding fault phase loss to find out the cause of phase loss overhaul the measurement value of line protector is improper modify the appropriate amount to use agriculture Food and industrial wastes (such as sugar beet, wood chip and food residue) are used as raw materials for packaging plastics. For thyristor failure power-off inspection, refer to the thyristor inspection procedure. Single phase input power failure troubleshooting input power failure psb1000 main circuit board failure power-off replacement of main circuit board, Refer to the thyristor replacement procedure

motor overload trip during starting

"fault" and "overload" lights on

improper adjustment of overload motor overload reduce motor load limit current too small increase motor current limit starting adjustment improper readjustment of motor overload trip during starting operation

"fault" and "overload" lights on

motor overload, During full speed operation, the current exceeds the limit

reduce the load overload, adjust the overload improperly, reset the overload, and the thermal relay trips

"fault" and "overheating" lights are on

there is too much dust on the radiator, clean the radiator with high-pressure air after power failure (80 ~ 100psi clean and dry air)

the fan does not work. If the fan is powered, replace the fan, No power maintenance power supply

over current means that the operating current does not exceed the rated value, and the ambient temperature exceeds 120 ℉ (panel type) or 104 ℉ (sealed type)

install the device in a low temperature environment, Do not exceed the rated temperature

the motor does not start. All the indicator lights are off. "Power" light is off

"start" light is off

"fault" and "lack of phase" lights are on

"fault" and "short circuit SCR" lights are on

there is no control power on the control board (tcb2000 board)

supply power between 1 and 9 contacts of tb1 on the tcb2000 control board

control power transformer failure or control power melting has brought new changes to the global plastic machine market pattern; Industrial structure adjustment continuously speed up the fuse fault

replace the control power transformer or control power fuse after power failure

correct the wrong wiring of the starting line after power failure. No starting command is applied. No three-phase power is supplied to the device. The three-phase power control board tcb2000 F2 fuse is fused. Replace the fuse main control board psb1000 fuse F1 fault. Replace and eliminate the fault main control board psb1000 fault. Replace the main control board controller logic circuit fault after power failure Repair the control board tcb2000, troubleshoot and replace the fuse thyristor, troubleshoot and replace the short-circuit SCR main control board psb1000, troubleshoot and replace the short-circuit SCR main control board psb1000, replace the main control board psb1000, continued table

problems, possible indicators, possible causes, solutions, motor vibration or high noise

"fault" and "phase loss" Light on

motor fault check motor and wiring thyristor fault after power failure, check thyristor thyristor control cathode fault repair and replace SCR main control board psb1000 fault replacement main control board psb1000 serious phase to phase current imbalance during startup and operation

fault "and" phase loss "lights on

motor or line fault repair line fault repair line replacement main control board psb1000 fault replacement main control board psb1000 motor stalling" fault "during operation And the "short circuit" light is on

note: This is a serious fault, which must be repaired and eliminated before restarting. Check and replace the main control board psb1000 after the grounding fault is powered off. When the main control board psb1000 is powered on, the control circuit fuse is blown

all indicators are off. The control circuit is short circuited, and the control voltage is improper

check and replace after the power is off, Supply correct voltage to the control board

(II) test of thyristor

disconnect any two-phase input line (L) connected to the thyristor and the corresponding output line (T). In order that the thyristor is not connected to the external circuit, disconnect the connection plugs between J1, J2 and J3 on the main circuit board psb1000 and the thyristor. Note the color line coding type connected with J1, J2 and J3. There are two types of plug structures, namely, four leads. The four color lines of the first structure are black, yellow, white and gray. The four color lines of the second structure are red, white, red and white. The inspection of thyristors consists of two steps. The first step is to test the resistance characteristics between the anode and cathode of the thyristor by testing the following resistance values. As listed in the table

meter multimeter to test the resistance between the anode and cathode of the thyristor

ohmmeter + probe ohmmeter - consult the manufacturer for normal probes L1 connector T1 connector 10K Ω 10K Ω L2 connector T2 connector 10K Ω 10K Ω L3 connector T3 connector 10K Ω 10K Ω the second step is to test the resistance between the control electrode of the thyristor and the cathode, as listed in the table. Insert an ohmmeter into the sockets of J1, J2 and J3 plugs unplugged from the main circuit board, measure the line resistance between the two wires of a plug, and then measure other plugs. The following table shows the range of resistance values for good or bad components

meter multimeter tests the resistance between the thyristor control electrode and the cathode

ohmmeter + probe ohmmeter - normal range of the probe abnormal range black yellow 5 ~ 100 Ω 5 or 100 Ω gray 5 ~ 100 Ω 5 or 100 Ω red, white, red, White wire ohmmeter + probe ohmmeter - normal abnormal range of the probe red white 5 ~ 100 Ω 5 or 100 Ω red white 5 ~ 100 Ω 5 or 100 Ω (III) replace the thyristor

ps1 series has two types of thyristors, depending on the rated power of the thyristor. The insulated thyristor is used for low-power equipment, and the hockey round thyristor is used for high-power equipment

1. Replace the insulated thyristor

as shown in the figure

(1) disconnect the power supply and control power supply, hang the warning sign of "do not switch on" and lock the control switch box, resulting in cracking and peeling of the concrete protective layer to avoid electric shock

figure insulated thyristor

warning: if the power supply and control power supply are not switched on, personal injury or death will be caused

(2) indicates the position of thyristor wiring

(3) remove the screws, wiring connectors and insulated wires on the thyristor

(4) keep the mounting surface of the prototype clean, free of dust, scratches and scratches

(5) heat conducting silica gel shall be coated on the length direction of the thyristor, and heat conducting silica gel shall also be coated on the base of the heat sink installed with the thyristor, so that the thyristor has good heat transfer characteristics

(6) reinstall the thyristor and tighten the wire head and screw. The table shows the recommended torque for different SCRs

table recommended torque table for fastening SCR

voltage (V) AC horsepower fixed screw conductive plate and power plug 2081 ~ 1044 lbs/in (0.5kg · m)

26 lbs/in (0.3KG · m) 20815 ~ 2044 lbs/in (0.5kg · m) 2401 ~ 1526 lbs/in (0.3KG · m) 24020 ~ 2544 lbs/in (0.5kg · M) 3801 ~ 2526 lbs/in (0.3KG · m) 38030 ~ 4044 lbs/in(0.5kg · m) 4151 ~ 2526 lbs/in (0.3KG · m) 41530 ~ 4044 lbs/in (0.5kg · m) 4801 ~ 3026 lbs/in (0.3KG · m) 48040 ~ 5044 lbs/in (0.5kg · m) 5751 ~ 4026 lbs/in (0.3KG · m) 57550 ~ 7544 lbs/in (0.5kg · m) (7) reconnect the conductive plate, connector and wire, check whether the control electrode and cathode wiring of the thyristor are correct, and check the wiring of J1, J2 and J3 with a meter

table quick reference table for connection between main circuit board and thyristor

main circuit board J1, J2, J3 and thyristor connection point lead 1 load end control pole lead 2 load end cathode lead 5 line end control pole lead 6 line end cathode (8) after all wiring is checked to be correct, turn on the power supply to detect the equipment

2. Replace the hockey round thyristor

(1) disconnect the power supply and control power supply, hang the warning sign of "do not switch on" and lock the control switch box to avoid electric shock

warning: personal injury or death may be caused if the power supply and control power supply are not switched on

(2) motortronics uses two different types of thyristor clamping plates and is equipped with measuring devices to display the installation torque used. The first torque measuring device is the rotating washer. When the appropriate torque is applied, the rotating washer starts to loosen. When it can be rotated by hand, stop exerting force. The second torque measuring device is to install the step indicator at the end of the lever. Before removing the splint, the position of the step indicator should be recorded so that it is easy to recover to the appropriate torque after replacing the thyristor

(3) record the connection position with the thyristor

(4) remove the power wiring board, mov (metal oxide rheostat), shock absorber, printed circuit board and some wires connected to the thyristor. Note that before removing the components, write down their location drawings for reinstallation

(5) record the position of the torque indicator on the thyristor clamp plate, and then remove the upper thyristor radiator

(6) remove the damaged thyristor and note the direction of the thyristor. The new thyristor should be installed in the same direction

(7) keep the thyristor mounting surface, tools and hands clean without dust, nicks and scratches. Do not polish the mounting surface with sandpaper. If necessary, clean the radiator with very fine high-grade metal wool before installing a new thyristor

(8) both sides of the thyristor shall be evenly coated with a thin layer of heat conducting silica gel to reduce the air gap. The heat conducting silica gel shall be free of pollution

(9) install the locating pin at the bottom of the radiator and place it at the hole center of the thyristor so that the direction of the thyristor is the same as that before removal in step 6. Tighten the retainers evenly and carefully to achieve the same torque. Tighten the nut one quarter turn at a time, and adjust the U-clamp until the appropriate torque is reached. Check the gauge every time you tighten it, or rotate the washer to prevent the thyristor from exceeding the torque. The reading of the torque indicator shall be the same as the scale position recorded in (2). If it is a rotary washer type, keep the washer rotating freely after tightening the retainer. Only by adjusting the appropriate clamping torque can the thyristor in the radiator work safely

check the main circuit board wiring with the meter

check the J1, J2 and J3 wiring with the meter

(11) conduct power on test after confirming that the wiring is correct

(IV) replace the printed circuit board

the printed circuit board cannot be repaired on site. In case of failure, replace the whole circuit board according to the following steps

(1) remove the three-phase power supply and control power supply of the device

(2) unplug the plug and mark the serial number of the plug connected to the connector

(3) remove the wiring from the wiring terminal block on the printed circuit board and mark the serial number of the wiring

(4) write down the settings of potentiometer, fault relay and programmable jumper plug

(5) remove the set screw

(6) remove the old printed circuit board

(7) install the new printed circuit board

(8) install the fixing screw

(9) set the potentiometer and fault relay. The programmable jumper plug is the same as the old circuit board

(10) connect the terminal controller connection and mark the connection serial number

(11) installation